This is a wall-sleeve air conditioner and electric-heat unit built for hotel rooms, dorms, and commercial spaces on a 265V electrical circuit. It's designed for property managers and facility owners who need self-contained, per-room cooling and heating without central ductwork.
The HEC094J35AXXX is a 265V PTAC with a 3.7 kW electric heat strip, built for hospitality and commercial applications where per-room, self-contained climate control is required. This chassis uses R-32 refrigerant and meets or exceeds ASHRAE 90.1 efficiency standards. Note: If you would like to review the manufacturer Product Specifications, Warranty, Brochure, etc., for this system, please refer to the "Resources (System Manuals and Warranty)" Tab above on this page.
Critical Fit & Power Requirements
- Wall sleeve opening: Standard 42 in wide x 16-1/16 in high — Wall Sleeve NOT included, sold separately (e.g., WS900E, WS900QW).
- Exterior Architectural Grille NOT included — sold separately (SGK, AGK, or PGK grille series).
- Voltage: 265V. Operating range 239V–292V minimum/maximum.
- Heater load: 3.7 kW, 1 stage, 3,770 total watts, 14.2 total amps.
- Electrical requirements: MCA 17.9A, MOP 20A. Power cord: NEMA 7-20P.
- Required for 265V operation: Amana sub-base (PTSB4**E series) or hard-wire kit PTPWHWK4 with disconnect switch PSHW04A — neither is included with the unit.
- Ships with factory-installed cartridge-style time-delay fuses (required for 265V models with heaters).
- Not compatible with 115V circuits.
- Not compatible with 230/208V circuits. The 230/208V version of this chassis is sold as model HEC093J — do not attempt to power this 265V unit from a 230/208V circuit or vice versa.
- Not a drop-in fit for non-standard or custom sleeve openings outside 42 in x 16-1/16 in.
On 265V hospitality installs, the receptacle configuration is the most common point of failure during turnover inspections. Verify the wall sub-base or hard-wire disconnect is rated for the NEMA 7-20P cord configuration before the drywall closes in — pulling a unit after finish work to correct a mismatched receptacle costs far more than a five-minute check with a NEMA receptacle chart. Long-term, an incorrectly matched receptacle on a 265V circuit is a fire risk, not just an inconvenience, since the factory time-delay fuses are sized to the correct MCA/MOP pairing (17.9A / 20A) and won't compensate for wiring errors upstream. Confirm receptacle and disconnect wiring against NEC Article 550 (or your local equivalent) before energizing the circuit, and document the inspection per your property's electrical maintenance log — this is standard practice for hospitality PM teams turning over multiple rooms on the same build cycle.
Key Benefits
- 9,200 BTU/h cooling capacity with a 12.7 EER rating.
- 3.7 kW electric heat strip delivers 12,600 BTU/h of heating at 265V.
- Dehumidification rate of 2 pints/hour supports humidity control in guest rooms.
- Fresh-air ventilation adjustable from 65 to 95 CFM.
- R-32 refrigerant, meets or exceeds ASHRAE 90.1 efficiency standards.
- Compact net weight of 102 lb simplifies handling during room turnovers.
| Spec | Value | Unit |
|---|---|---|
| Cooling Capacity | 9,200 | BTU/h |
| Heating Capacity (265V) | 12,600 | BTU/h |
| Electric Heat Strip Size | 3.7 | kW |
| Heat Stages | 1 | stage |
| EER | 12.7 | — |
| Voltage | 265 | V |
| Compressor Amps | 3.6 | A |
| Compressor Watts | 700 | W |
| Total Heater Watts | 3,770 | W |
| Total Amps (with heater) | 14.2 | A |
| MCA | 17.9 | A |
| MOP | 20 | A |
| NEMA Plug Type | 7-20P | — |
| CFM Wet (High/Low) | 290/264 | CFM |
| CFM Dry (High/Low) | 318/318 | CFM |
| Ventilation CFM | 65-95 | CFM |
| Dehumidification | 2 | pints/hr |
| Net Weight | 102 | lb |
| Ship Weight | 117 | lb |
| Refrigerant Type | R-32 | — |
| Wall Sleeve Dimensions | Standard 42 x 16-1/16 | in |
| Wall Sleeve Included | Not Included | — |
| Exterior Architectural Grille Included | Not Included | — |
Note: See "Resources (System Manuals and Warranty)" Tab above for full specifications.
Compatibility & Fitment
- Compatible with 265V commercial electrical circuits (239V–292V operating range) via NEMA 7-20P plug, when paired with the required Amana sub-base or hard-wire kit.
- Fits standard 42 in x 16-1/16 in wall sleeve openings (WS900E, WS900QW, and compatible Amana sleeve series).
- Not compatible with 115V circuits.
- Not compatible with 230/208V circuits — use sibling model HEC093J for 230/208V installations.
- Wall Sleeve NOT included — must be ordered separately.
- Exterior Architectural Grille NOT included — must be ordered separately.
- Not a drop-in replacement for non-standard or custom sleeve openings.
| Attribute | Detail |
|---|---|
| Refrigerant Type | R-32 |
| Efficiency Standard | Meets or exceeds ASHRAE 90.1 |
| Overcurrent Protection (265V with heater) | Factory-installed cartridge-style time-delay fuses |
| Power Cord Standard | NEMA 7-20P (265V heater configuration; LCDI cord standard applies only to units under 250V and does not apply to this 265V unit) |
| Required Sub-Base/Hard-Wire Kit | Amana PTSB4**E sub-base, or PTPWHWK4 hard-wire kit with PSHW04A disconnect (sold separately) |
FAQ
Is the wall sleeve included with this unit?
No. The wall sleeve is sold separately. This unit is designed to fit a standard 42 in x 16-1/16 in wall sleeve opening (WS900E, WS900QW, or compatible Amana sleeve models).
What breaker size and plug type does this unit require?
This 265V configuration with the 3.7 kW heater has an MCA of 17.9A and a MOP of 20A, and ships with a NEMA 7-20P power cord.
Can this be hardwired for 265V commercial applications?
Yes. All 265V Amana PTAC models require either an Amana sub-base (PTSB4**E series) or the PTPWHWK4 hard-wire kit paired with the PSHW04A disconnect switch. Neither is included with the unit and must be ordered separately.
Does this require a licensed electrician or HVAC professional to install and keep the warranty valid?
265V units require licensed electrical work for sub-base or hard-wire kit installation given the voltage and factory-installed cartridge-style time-delay fuses. Refer to the warranty document in the Resources tab for exact installation requirements tied to warranty validity.
Will this fit a standard 42-inch by 16-inch wall sleeve opening?
Yes. This chassis is built for the industry-standard 42 in wide x 16-1/16 in high wall sleeve opening. It is not a drop-in fit for non-standard or custom sleeve openings.
Warranty & Registration
This unit carries a 1-Year Repair/Replace warranty and a 5-Year Parts Limited Warranty. Commercial hospitality use may carry different terms than residential use — exact language, exclusions, and registration steps are detailed in the warranty document under the "Resources (System Manuals and Warranty)" Tab above. Review that document before installation to confirm coverage terms specific to your application. If you have questions about what's covered, ask us before you order — we always reply back.