This is a wall-sleeve air conditioner and electric heater built for hotel rooms, apartments, and additions where central ductwork isn't an option. It's a 265V commercial unit, so it's meant for properties already wired for 265V circuits — not for typical residential 230/208V or 115V outlets.
The PMC074J35AXXX is a 265V packaged terminal air conditioner with electric heat, intended for hospitality and multi-family properties running commercial 265V electrical service. It pairs a 6,800 BTU cooling chassis with a 3.7 kW electric heat strip for single-stage supplemental heat. Note: If you would like to review the manufacturer Product Specifications, Warranty, Brochure, etc., for this system, please refer to the "Resources (System Manuals and Warranty)" Tab above on this page.
- Wall Sleeve opening: Industry-standard 42 in wide x 16-1/16 in high (sleeve required for install, sold separately)
- Voltage: 265V — min 239V / max 292V operating range
- Electric Heat: 3.7 kW, single stage, 12,600 BTU/h heating output at 265V
- Total Amps (with heat): 14.2A; MCA: 17.9A; MOP: 20A
- NEMA Plug Type: 7-20P power cord
- Wall Sleeve is NOT included. Exterior Architectural Grille is NOT included. Both must be ordered separately.
- 265V models require an Amana brand sub-base (PTSB4**E series) or the PTPWHWK4 hard-wire kit with PSHW04A disconnect switch — sold separately, not included with this unit.
- Not compatible with 115V circuits.
- Not compatible with 230/208V circuits. If your building runs 230/208V, see the sibling chassis PMC073J instead.
- Not a drop-in fit for non-standard sleeve openings outside the 42 in x 16-1/16 in standard.
- Compressor draws 3.8A / 535W at 265V, independent of heater load
- Fresh air ventilation CFM of 25-35 supports code-required make-up air in tightly sealed guest rooms
- Refrigerant: R-32
- Meets or exceeds ASHRAE 90.1 efficiency standards
- EER of 12.7 on the cooling chassis
- 342 CFM indoor airflow
| Spec | Value | Unit |
|---|---|---|
| Cooling Capacity | 6,800 | BTU/h |
| Heating Capacity (265V) | 12,600 | BTU/h |
| Electric Heat Strip | 3.7 | kW |
| Heat Stages | 1 | stage |
| Voltage | 265 | V |
| EER | 12.7 | BTU/Wh |
| Compressor Amps | 3.8 | A |
| Compressor Watts | 535 | W |
| Total Heat Watts | 3,770 | W |
| Total Amps (with Heat) | 14.2 | A |
| MCA | 17.9 | A |
| MOP | 20 | A |
| NEMA Plug Type | 7-20P | |
| CFM | 342 | CFM |
| Fresh Air CFM | 25-35 | CFM |
| Refrigerant Type | R-32 | |
| Wall Sleeve Dimensions | Standard 42 in x 16-1/16 in | |
| Wall Sleeve Included | Not Included | |
| Exterior Architectural Grille Included | Not Included | |
Note: See "Resources (System Manuals and Warranty)" Tab above for full specifications.
- Fits industry-standard 42 in x 16-1/16 in wall sleeve openings, including WS900E and WS900QW sleeves
- Compatible with 265V commercial electrical circuits, min 239V / max 292V, via 7-20P plug when paired with the required Amana sub-base or hard-wire kit
- Wall Sleeve NOT included — order separately (WS900E, WS900QW, WS900SC seacoast, WS900GS sound-isolation, or deep-wall variants as needed)
- Exterior Architectural Grille NOT included — order separately (SGK stamped, AGK extruded aluminum, or PGK polymer)
- Required sub-base (PTSB4**E) or hard-wire kit (PTPWHWK4 with PSHW04A disconnect) NOT included
- Not compatible with 115V circuits or 230/208V circuits — for 230/208V service, use sibling chassis PMC073J instead
- Not a drop-in replacement for non-standard or custom sleeve openings
| Item | Detail |
|---|---|
| Refrigerant Type | R-32 |
| Efficiency Standard | Meets or exceeds ASHRAE 90.1 |
| Overcurrent Protection (265V) | Factory-installed cartridge-style time-delay fuses |
| LCDI Cord Applicability | Not applicable — LCDI cords apply only to units under 250V; this is a 265V unit |
| Electrical Compliance | UL 484 (cord-connected units under 250V); NEC-compliant sub-base/hard-wire installation required for 265V |
Frequently Asked Questions
Is the wall sleeve included with this unit?
No. The wall sleeve is sold separately. This unit installs into an industry-standard 42 in wide x 16-1/16 in high sleeve opening, such as the WS900E or WS900QW series.
What breaker size and plug type does this unit require?
This 265V unit with 3.7 kW electric heat has an MCA of 17.9 amps and an MOP of 20 amps. It ships with a 7-20P power cord.
Can this be hardwired for 265V commercial applications?
Yes, but it requires an Amana brand sub-base (PTSB4**E series) or the PTPWHWK4 hard-wire kit with PSHW04A disconnect switch. Both are sold separately.
Does this require a licensed electrician or HVAC professional to install and keep the warranty valid?
[NEEDS VERIFICATION] Installer licensing requirements for warranty validity are not specified in the provided source files. Refer to the warranty PDF in the Resources tab for exact terms.
Will this fit a standard 42-inch by 16-inch wall sleeve opening?
Yes. This chassis fits the industry-standard 42 in x 16-1/16 in wall sleeve opening. It is not a drop-in fit for non-standard or custom sleeve openings.
Warranty & Registration
This unit carries a 1-Year Repair/Replace warranty and a 5-Year Parts Limited Warranty on covered components. Exact terms, including commercial hospitality versus residential usage limits, are detailed in the warranty PDF under the "Resources (System Manuals and Warranty)" Tab above. Ask us before you order if you need help confirming coverage for a specific property type — we always reply back.