This is a wall-sleeve air conditioner and electric-heat unit for hotel rooms, apartments, assisted living suites, or additions where central ductwork isn't available. It's built for property managers and homeowners who need self-contained, per-room climate control on a standard 230/208V circuit.
The PTC093J50AXXX is a packaged terminal air conditioner with electric resistance heat, built for hospitality rooms, multifamily units, and additions where a self-contained 230/208V climate system replaces central ductwork. It carries a factory EER of 12.1/12.2 and meets or exceeds ASHRAE 90.1. Note: If you would like to review the manufacturer Product Specifications, Warranty, Brochure, etc., for this system, please refer to the "Resources (System Manuals and Warranty)" Tab above on this page.
- Wall sleeve opening required: industry-standard 42 in wide x 16-1/16 in high.
- Voltage: 230/208V. Amperage (with heater): 22.1/20.0A total; MCA 27.6A; MOP 30A.
- Power cord/plug: factory-installed NEMA 6-30P, with LCDI device per UL 484 (applies to all units under 250V).
- Wall Sleeve is NOT included and must be ordered separately (e.g., Amana WS900E or WS900QW).
- Exterior Architectural Grille is NOT included and must be ordered separately (SGK, AGK, or PGK series).
- Not compatible with 115V circuits.
- Not compatible with 265V circuits — the 265V commercial sibling PTC094J requires an Amana sub-base (PTSB4**E) or hard-wire kit PTPWHWK4 with disconnect switch PSHW04A. This 230/208V unit does not use a sub-base and does not require hardwiring.
- Not a drop-in fit for non-standard or custom sleeve openings.
Sleeve pitch is the friction point that generates callbacks on this chassis. Because the PTC093J condensate path relies on gravity drainage through the sleeve base, an installer who sets the sleeve dead-level will see water track backward into the wall cavity during high-humidity cooling cycles. Pitch the sleeve 1/4 bubble toward the outside wall — check it with a torpedo level set lengthwise on the sleeve rail, not on the unit chassis — before securing the framing. This keeps condensate draining outward through the drain kit (DK900D for WS900E, DK900QW-matched drain for WS900QW) instead of into the drywall or subfloor. On the electrical side, confirm the receptacle in the sub-base or wall box is a NEMA 6-30R matched to the unit's factory 6-30P cord — a mismatched 6-20R receptacle on a unit drawing 27.6A MCA is a common property-management complaint and a NEC Article 210 receptacle-rating violation, not just an inconvenience.
- Single-stage 5.0/4.1 kW electric heat strip delivers 17,100/14,000 BTU/h heating at 230V/208V respectively.
- EER of 12.1 (230V) / 12.2 (208V) for cooling efficiency at rated conditions.
- Dehumidification rate of 2 pints/hr supports guest-room and multifamily humidity control.
- 65 CFM fresh-air ventilation option for make-up air in tightly sealed rooms.
- R-32 refrigerant charge, per manufacturer catalog note.
- Compact 102 lb net weight (117 lb shipped) simplifies chassis swap-outs in occupied buildings.
| Spec | Value | Unit |
|---|---|---|
| Cooling Capacity (230V/208V) | 9,200/9,000 | BTU/h |
| Heating Capacity (230V/208V) | 17,100/14,000 | BTU/h |
| Electric Heat Strip Size (230V/208V) | 5.0/4.1 | kW |
| Heat Stages | 1 | stage |
| Voltage | 230/208 | V |
| Compressor Amps (230V/208V) | 4.1/4.1 | A |
| Compressor Watts (230V/208V) | 760/750 | W |
| Total Heater Amps (230V/208V) | 22.1/20.0 | A |
| Total Heater Watts (230V/208V) | 5,070/4,160 | W |
| MCA | 27.6 | A |
| MOP | 30 | A |
| NEMA Plug Type | 6-30P | - |
| EER (230V/208V) | 12.1/12.2 | BTU/Wh |
| CFM Wet (High/Low) | 290/264 | CFM |
| CFM Dry (High/Low) | 321/295 | CFM |
| Ventilation CFM | 65 | CFM |
| Dehumidification Rate | 2 | pints/hr |
| Net Weight | 102 | lb |
| Shipping Weight | 117 | lb |
| Refrigerant Type | R-32 | - |
| Wall Sleeve Dimensions | 42 x 16-1/16 | in (W x H) |
| Wall Sleeve Included | Not Included | - |
| Exterior Architectural Grille Included | Not Included | - |
Note: See "Resources (System Manuals and Warranty)" Tab above for full specifications.
- Compatible with 230/208V circuits via factory-installed NEMA 6-30P plug.
- Fits industry-standard wall sleeve openings of 42 in wide x 16-1/16 in high, including Amana WS900E and WS900QW sleeves.
- Not compatible with 115V circuits.
- Not compatible with 265V circuits — that voltage class requires the PTC094J chassis with an Amana sub-base (PTSB4**E) or hard-wire kit PTPWHWK4 plus disconnect switch PSHW04A.
- Wall Sleeve NOT included — order separately.
- Exterior Architectural Grille NOT included — order separately (SGK, AGK, or PGK series).
- Not a drop-in replacement for non-standard or custom sleeve openings.
| Compliance Item | Value |
|---|---|
| Refrigerant Type | R-32 |
| Efficiency Standard | Meets or exceeds ASHRAE 90.1 |
| Power Cord Compliance | LCDI power cord per UL 484 (units under 250V) |
| Voltage Operating Range | 197V min / 253V max (230/208V models) |
| Overcurrent Protection (no heater) | 15A for all units without electric heaters |
Frequently Asked Questions
Is the wall sleeve included with this unit?
No. The wall sleeve is sold separately. This unit is designed to fit an industry-standard 42 in wide x 16-1/16 in high sleeve opening, such as the Amana WS900E or WS900QW.
What breaker size and plug type does this unit require?
This configuration has an MCA of 27.6A and a maximum overcurrent protection (MOP) rating of 30A, and it ships with a factory-installed 6-30P NEMA plug for a 230/208V circuit.
Can this be hardwired for 265V commercial applications?
No. This is a 230/208V unit and is not rated for 265V circuits. The 265V commercial sibling chassis (PTC094J) is required for 265V applications, and it must be paired with an Amana sub-base (PTSB4**E) or hard-wire kit PTPWHWK4 with disconnect switch PSHW04A.
Does this require a licensed electrician or HVAC professional to install and keep the warranty valid?
[NEEDS VERIFICATION] — installation labor requirements are not specified in the provided data. Refer to the warranty PDF in the Resources tab for exact terms.
Will this fit a standard 42-inch by 16-inch wall sleeve opening?
Yes. This chassis fits the industry-standard 42 in wide x 16-1/16 in high wall sleeve opening. It is not a drop-in fit for non-standard or custom sleeve dimensions.
Warranty & Registration
This unit carries a 1-Year Repair/Replace warranty and a 5-Year Parts Limited Warranty on the sealed system, per Amana's published warranty badge assets. Exact terms, including any distinction between residential and commercial hospitality usage, are defined in the manufacturer warranty document — refer to the "Resources (System Manuals and Warranty)" Tab above on this page for the full warranty PDF before you install or register the unit. If you have questions about coverage on a hospitality or multifamily install, ask us before you order — we always reply back.